Installation, Operation
& Service Manual
Models UHA[S]
150, 175, 200, 225
250, 300, 350, 400
P/N 111101NA 06/08 Rev. E
UHA-Series
Tubular Unit Heaters
(Standard Range)
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Leave the building.
6. Immediately call your local gas
supplier after leaving the building.
Follow the gas suppliers
instructions.
7. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
WARNING
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the Installation, Operation and Service
Manual thoroughly before installing or servicing
this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Roberts-Gordon LLC
1250 William Street
P. O. Box 4 4
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
www.rg-inc.com
© 2008 Roberts-Gordon LLC
Quality in Any Language™
Combat
®
Vista de página 0
1 2 3 4 5 6 ... 51 52

Resumo do Conteúdo

Página 1 - (Standard Range)

Installation, Operation& Service ManualModels UHA[S]150, 175, 200, 225250, 300, 350, 400P/N 111101NA 06/08 Rev. EUHA-SeriesTubular Unit Heaters(St

Página 2

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL4 Figure 1: Installation Clearances and Clearances to CombustiblesWARNINGFire HazardS

Página 3 - Roberts-Gordon LLC

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES5SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES4.1 Gas CodesThe type of gas appearing on the nam

Página 4

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL6 SECTION 5: MAJOR COMPONENTS 5.1 General Heaters are designed for installation above

Página 5 - TABLE OF FIGURES

SECTION 6: VENTING7SECTION 6: VENTING6.1 VentingThis heater must be vented in accordance with the rules contained in this manual and with the followin

Página 6

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL8 6.2.2 Separated Combustion Heaters (Models UHAS 150 - 400)The heaters are

Página 7 - SECTION 1: HEATER SAFETY

SECTION 6: VENTING96.7 Vent MaterialVent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely

Página 8

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL10 Figure 5: Standard Vented Heater - Common Vertical Vent TerminationRoof18"

Página 9 - RITICAL CONSIDERATIONS

SECTION 6: VENTING11Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent TerminationFigure 7: Concentric Vent BoxVentTerminationListed

Página 10 - Installation Clearances

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL12 Figure 8: Concentric Vertical and Horizontal Vent Termination - Separated Combusti

Página 11

SECTION 7: AIR SUPPLY13SECTION 7: AIR SUPPLY7.1 Separated Combustion InstallationWhen installed as a separated combustion heater (UHAS), the air for c

Página 13 - SECTION 6: VENTING

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL14 SECTION 8: GAS PIPINGIt is important that the gas supply pipe and the electrical c

Página 14

SECTION 9: WIRING15SECTION 9: WIRINGAll heater models require constant 120 V 60 Hz 1Ø power supply. Check heater(s) rating plate for electrical rating

Página 15

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL16 9.3 UHA[S] Series Internal Wiring DiagramBLUEBLACKBLACKORANGEORANGEYELLOWBROWNBLAC

Página 16

SECTION 9: WIRING179.4 UHA[S] Series Ladder Wiring DiagramNOTE:For field wiring into service junction box, or if any of the original wire supplied wit

Página 17 - Figure 7: Concentric Vent Box

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL18 9.5 Electrical Connection to the HeaterNote: Junction box is not provided with hea

Página 18 - 8" Dia. Single Wall

SECTION 10: OPERATION AND MAINTENANCE19SECTION 10: OPERATION AND MAINTENANCEInstallation, service, and annual inspection of the heater must be done by

Página 19 - SECTION 7: AIR SUPPLY

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL20 Figure 10: Automatic Burner Control SequenceFigure 11: Gas Valve for Models UHA[S]

Página 20 - Fire Hazard

SECTION 10: OPERATION AND MAINTENANCE2110.2.2 Start-Up the Gas Valve (All Gases)10.2.2.1 Check Burner Gas Pressure1. Remove the plug in the outlet (bu

Página 21 - SECTION 9: WIRING

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL22 SECTION 11: USER INSTRUCTIONS11.1 User InstructionsThe UHA[S] Series heaters are f

Página 22

SECTION 11: USER INSTRUCTIONS23WARNINGFOR YOUR SAFETYIf you smell gas:1. Open windows.2. DO NOT try to light any appliance.3. DO NOT use electrical sw

Página 23

© 2008 Roberts-Gordon LLCAll rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any

Página 24

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL24 SECTION 12: SERVICING12.1 Servicing InstructionsAfter start-up, the heater will re

Página 25 - Cut Hazard

SECTION 12: SERVICING2512.8 Maintenance ChecklistInstallation Code and Annual Inspections: All installations and service of ROBERTS GORDON® equipment

Página 26 - End View

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL26 Burner Observation WindowMake sure it is clean and free of cracks or holes.Clean a

Página 27 - PERATION AND MAINTENANCE

SECTION 13: TROUBLESHOOTING27SECTION 13: TROUBLESHOOTING13.1 GeneralEnsure proper air flow clearance for axial fan. Open louvers slightly.Replace axia

Página 28 - Electrical Shock Hazard

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL28 13.2 Troubleshooting For Automatic Ignition Burner SystemsIf problems persist, con

Página 29 - SECTION 11: USER INSTRUCTIONS

SECTION 13: TROUBLESHOOTING2913.3 Troubleshooting for Flame Supervision SystemNOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3

Página 30

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL30 13.4 Troubleshooting for Gas Valves13.5 Troubleshooting for Flue Blower Valve faul

Página 31 - SECTION 12: SERVICING

SECTION 14: REPLACEMENT PARTS31SECTION 14: REPLACEMENT PARTSSee warnings and notes on Page 24, Section 12 before removing or replacing parts.Burner Co

Página 32

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL32 14.2 Burner Compartment14.2.1 Burner InjectorsRemove flexibleair duct from spigotR

Página 33 - 13.1 General

SECTION 14: REPLACEMENT PARTS3314.3 Ignition Electrode and Flame ProbeDescription Part Number Qty.Spark Electrode 90427411 1Automatic Ignition Flame P

Página 35

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL34 14.4 Heat Exchanger The standard heat exchanger assembly is compossed of multiple

Página 36

SECTION 14: REPLACEMENT PARTS3514.6 Flue Blower IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING

Página 37 - SECTION 14: REPLACEMENT PARTS

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL36 14.7 Pressure SwitchPull off 3 way connector. Spring open plastic clips of mountin

Página 38

SECTION 14: REPLACEMENT PARTS3714.9.1 Fan Removal and Replacement14.9.2 To Replace the Fan Assembly• To replace the fan assembly, reverse the procedur

Página 39

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL38 SECTION 15: SPECIFICATIONS15.1 Standard (Models 150 - 400) UHA[S] Series Dimension

Página 40 - Horizontal

SECTION 15: SPECIFICATIONS3915.2 General Technical Data Table (All Models)*Do not exceed the maximum length of flue stated or heater may not operate p

Página 41

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL40

Página 42

SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SERIES WARRANTY41SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SERIES WARRANTYROBERTS-GORDON WILL PAY FOR:Wi

Página 45 - PECIFICATIONS

TABLE OF FIGURESFigure 1: Installation Clearances and Clearances to Combustibles ... 4Figure 2:

Página 48

10'(3 m)WARNING© 2007 Roberts-Gordon, LLC www.rg-inc.com

Página 50

SECTION 1: HEATER SAFETY1SECTION 1: HEATER SAFETYYour Safety is Important to Us!This symbol is used throughout the manual to notify you of possible fi

Página 51

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL2 SECTION 2: INSTALLER RESPONSIBILITYThe installer is responsible for the following:•

Página 52 - Max. Mounting Height*

SECTION 3: CRITICAL CONSIDERATIONS3SECTION 3: CRITICAL CONSIDERATIONS3.1 Basic InformationUHA[S] heaters have automatic ignition burners for ON/OFF op